Box Fill & Pull Boxes
Outlet/device/junction box fill per NEC 314.16 (2020), and pull/junction box sizing for 4 AWG and larger per 314.28.
1 · What's in the box
Insulated conductors (count each one entering & spliced/terminated, or passing through)
An unbroken conductor looped 12 in. or longer (twice the 300.14 length) counts as 2 — enter it twice. Pigtails, jumpers and fixture wires that don't leave the box are not counted, and up to four fixture wires smaller than 14 AWG plus an EGC from a domed canopy are exempt (314.16(B)(1) Exc.).
Devices / yokes (2 × largest conductor connected to the device)
Other allowances
2 · Box choice
314.16(A): rings, extensions and covers count only when marked with their volume (or made from boxes listed in Table 314.16(A)). Use the marked number — values above are typical.
Metal boxes — Table 314.16(A)
Nonmetallic boxes — typical marked volumes
3 · Reverse: max conductors of one size
Count only — subtract 2 for each device, 1 for clamps, 1 per fitting type, and EGC allowances (Table 314.16(A) assumes none of these).
4 · Pull & junction boxes (314.28, 4 AWG and larger)
Straight pull — 314.28(A)(1)
Angle or U pull — 314.28(A)(2)
Enter raceways entering ONE wall, comma-separated. Use a second row if there are two rows on that wall.