Dead Outlet / Lost Circuit
A systematic way to find why an outlet, switch, or whole circuit has gone dead. Related guides: open / backfed neutral, tripping breaker, flickering or dimming lights.
⚠ Safety. Treat every conductor as live until you prove otherwise. Lock out the breaker once you have identified it, verify dead, and use a known-live proving source for your tester. Multi-wire branch circuits can remain live on the other leg when one breaker is off.
General field practice for qualified electricians. The equipment manufacturer's instructions, your adopted code edition, and the AHJ govern where they differ.
1 · Confirm it is actually dead
- Try more than one outlet or lamp on the circuit, and try a known-good cord or bulb so you are not chasing a bad device.
- Check GFCI and AFCI devices that may be upstream — press Reset on every GFCI in the area (bath, garage, kitchen, outdoor, basement) and any AFCI/GFCI breaker in the panel. A single tripped GFCI can kill several downstream receptacles.
- Look at the panel: tripped breaker (not just off), a breaker that will not reset, or a loose handle. If it trips immediately, stop and use the tripping-breaker guide — do not keep resetting into a fault.
2 · Map the circuit
- Identify the breaker from the directory, then confirm by dropping the breaker and checking the dead outlets (or using a circuit tracer). Update the directory when you are done (408.4).
- Note shared neutrals (MWBC): two hots, one neutral, usually a handle-tied or two-pole breaker. Measuring 240 V between hots and ~120 V to neutral at a live device is the clue. Opening only one pole can energize the neutral from the other leg.
- List every device on the run: receptacles, switches, lights, and junction boxes. Dead outlets “downstream of the first dead one” often point to an open backstab or a loose splice at the last working box — or at the first dead box.
3 · Test in order
- At the panel (cover off only if you are qualified and using the required PPE): voltage on the breaker output to neutral and to ground; tightness of the breaker on the bus and of the conductor in the lug; a tripped AFCI/GFCI breaker that looks “on” until you cycle it fully off and on.
- At the first dead outlet: with the circuit re-energized and safe work practices, measure hot to neutral, hot to ground, and neutral to ground. 120 V hot-ground and 0 V hot-neutral is an open neutral (see open-neutral guide). 0 V everywhere may be an open hot, a tripped upstream device, or a lost feeder in a junction.
- Open the last working box and the first dead box (power off, verify). Look for backstabbed conductors that have pulled out, loose wire nuts, a broken tab on a receptacle that was feeding downstream, a nicked conductor in a staple, or a switch-loop that was mistaken for a feed.
- Renovation work, doorbell transformers, and “someone added a receptacle” junctions above drop ceilings or under insulation are common lost-circuit hiding places.
4 · After the repair
Retest every outlet on the circuit (hot-neutral, hot-ground, polarity, and GFCI where required). Tug-test splices, torque devices to the listed value, and restore any AFCI/GFCI protection the adopted edition requires. If the circuit died after water, heat, or a burning smell, inspect the entire run before you call it fixed.
Reference only — not engineering, legal, or code-compliance advice. Results are estimates for qualified persons and must be verified against the NEC edition adopted where the work is done (your selected edition), manufacturer instructions, and the local AHJ. Use is subject to the Terms of Use & Disclaimer. — Morningstar Electric LLC