GFCI / AFCI Breaker Testing & Trip Codes
⌂ Home

GFCI / AFCI Breaker Testing & Trip Codes

General field practice for qualified electricians. The equipment manufacturer's instructions, your adopted code edition, and the AHJ govern where they differ.

LED and trip-indicator codes differ by brand, product line, and generation. Each brand's table below is copied from the manufacturer document cited next to it. Match the catalog number and generation on the breaker label, and follow the instruction sheet that came with the breaker if it differs. Brands and lines marked ✖ NOT verified were not checked against a manufacturer document.

1 · Testing basics

2 · Square D (Schneider Electric) — QO & Homeline AF / AFGF with Time Saving Diagnostics

✔ verified from manufacturer document[4][5]

When you turn the breaker back on, its LED shows the cause of the last trip. If a code is stored, tap and release TEST quickly to replay the LED pattern without tripping the breaker.

LED at power-upLast trip
Solid ON 10 s, then OFFArc fault
2 pulsesGround fault
4 pulsesGrounded neutral
7 pulsesArc-fault protection unresponsive. Schneider says to contact them for a replacement breaker (888-778-2733).
LED does not turn onNo fault stored, thermal overload, or short circuit

TIME SAVER fault indication (hold-TEST method, AFGF)

  1. Turn the breaker OFF.
  2. Press and hold TEST.
  3. Keep holding TEST and move the handle to ON.
  4. Note when it trips: instantly (<1 s) = fault to ground; 2 s = arc fault; 5 s = procedure complete (no fault, thermal overload, or short circuit); 10 s = out of memory.

To clear the stored indication, run the procedure 6 times in total. A trip at 5 s confirms it's done. The breaker also clears itself after 27 days of continuous power.[4] Older Square D CAFI/DF breakers without the TSD LED: ✖ NOT verified here. Use that breaker's instruction bulletin.[6]

3 · Eaton — Type CH & BR dual-function AF/GF

✔ verified from manufacturer document[7][8]

Startup blinks (within ½ s of turn-on): 1 quick blink = electronic overload detection OFF (uncommon); 2 = 15 A handle rating; 3 = 20 A handle rating. About 3 s later the red LED blinks the trip code, repeating 30 times with a pause between repeats.

BlinksTrip causeEaton's resolution
1Series arc (low current)Find and repair or replace the equipment, cord, or loose connection
2Parallel arc (high current)Find the damaged wiring (nail, screw, staple) and replace it
3Short delay (electronic backup to short-circuit trip)Find and repair the short
4Overvoltage (160 V rms or more)Check utility power for phase imbalance or a lost neutral
5Ground faultFind and repair the leakage path
6Self-test failureReplace the breaker

No code is recorded for a thermal overload, a mechanical short-circuit trip, a TEST press, or switching OFF by hand. In those cases the breaker shows the last recorded code. A new breaker shows its factory-test code.

Recall the last code

  1. Handle OFF.
  2. Press and hold TEST.
  3. Handle ON.
  4. Release TEST. The code blinks 30 times, starting about 3 s later.

If it trips before you can read the code, disconnect the branch hot and neutral and try again. The code is erased 2 hours after a recall, so write it down.[7]

4 · Siemens — AFCI / dual-function (trip-indicator LEDs)

✔ verified from manufacturer document[9][1][10]

Turn the breaker OFF, then ON, and watch the LEDs. On dual-function breakers they show for about 5 s each time you turn it ON, for up to 30 days after the last trip.[1] Check the generation on the label.

1-pole Gen 1–3A CAFCI and Gen 2 DF
LED 1LED 2Last trip
OffOffOvercurrent
OnOffArc to neutral or series arc fault
OnOnGround fault or arc to ground
1-pole Gen 3B CAFCI (one LED, no GF protection)
OffOvercurrent
OnArc to neutral, arc to ground, or series arc
2-pole Gen 1–3A CAFCI
123Last trip
OffOffOffOvercurrent
OnOffOffArc to neutral or series arc (leg A)
OffOffOnArc to neutral or series arc (leg B)
OnOnOnGround fault or arc to ground
1-pole Gen 2 GFCI, 2-pole Gen 1B GFCI, 1-pole Gen 2 GFEP
OffOvercurrent or ground fault
BlinkingBreaker needs to be replaced

Older Gen 1–1B branch/feeder AFCIs and Gen 1 GFCIs use a yellow window or LED. See section 2.2 of the Siemens diagnostic guide.[9] On the dual-function install sheet, both LEDs blinking means replace the breaker. Clear the stored indication: handle OFF → press and hold the test button → handle ON → release after 3 s.[1][10]

5 · GE / ABB — Q-Line dual-function (DFCI, e.g., THQL…DF)

✔ verified from manufacturer document[2][11]

Test with the rocker: press toward AF to test arc-fault detection, or toward GF to test ground-fault detection. It passes if the TRIP flag appears. After you reset a tripped breaker, the LED in the trip-flag window shows:

After resetMeaning (ABB installation instructions)
ORANGE, then REDGround fault detected (from TEST or the load circuit)
ORANGE, then YELLOWArc fault detected (from TEST or the load circuit)
Trips again immediately after resetShort circuit, ground fault, or grounded neutral. If the fix doesn't work, the GF sensing may have failed.
Constantly blinking RED and YELLOW after push-to-testThe breaker has lost its ability to detect arc and ground faults. Replace it.

⚠ Sources disagree. ABB's Residential Electronic Circuit Interrupters brochure (1TQC1136E0002) lists "Orange-Red = arc fault, Orange-Yellow = ground fault," which is the reverse of the installation instructions above. Follow the instruction sheet that came with the breaker, or ask ABB (800-782-8061). Copy used: a third-party-hosted copy of ABB's DFCI installer instructions[2]. ABB's official library[11]. GE/ABB AFCI-only breakers (THQL…AF2) use a PAR ARC / SER ARC test rocker[12]. Their LED code table: ✖ NOT verified.

6 · Leviton — AFCI / GFCI / dual-function branch breakers

✔ verified from manufacturer document[3][13]

The LEDs are powered from the line side, so they stay lit while the breaker is tripped. The handle window color shows the status.

WindowAF LEDGF LEDStatus
GreenOffOffON
GreenON/OFF LED solid (smart breakers)Remote OFF
RedOffOffOverload or short-circuit trip
RedSolidOffSeries arc-fault trip
RedBlinking (1 s)OffParallel arc-fault trip
RedOffSolidGround-fault trip or grounded neutral
RedOffBlinking (0.5 s)Grounded neutral
RedOffBlinking (3 s)Neutral miswired
RedBlinking (0.1 s)Blinking (0.1 s)Electronics self-test failure. The breaker is locked out and must be replaced.
WhiteOffOffManual OFF

Reset: OFF, then ON. Leviton breakers won't reset if protection is compromised. Leviton's load-center sheet lists 1 s for the self-test-failure blink, and the dual-function instruction sheet lists 0.1 s. Go by the sheet for your breaker.[3][13]

7 · Not verified — use the breaker's own label or instructions

✖ NOT verified Murray, Crouse-Hinds, Westinghouse, Challenger, Federal Pacific, Zinsco, Wadsworth, Connecticut Electric and other classified replacements, older Cutler-Hammer and GE generations, and any Square D, Eaton, Siemens, GE/ABB, or Leviton line not listed above. No LED codes are given for these because none were checked against a manufacturer document.

Sources

  1. Siemens Dual Function AFCI/GFCI installation instructions (Pt. No. 812420A), distributor-hosted copy — https://cdn.gescan.com/PIM_Docs/Docs/STEP_ASSETS_PDF/299438938.pdf
  2. ABB/GE Dual Function Circuit Interrupter (DFCI) installer instructions, third-party-hosted copy — https://manualzz.com/doc/66001271/abb-dual-function-gfci-afci-ground-fault-and-combination-ar...
  3. Leviton 1-pole Dual-Function AFCI/GFCI branch circuit breaker instructions — https://leviton.com/content/dam/leviton/residential/product_documents/instruction_sheet/leviton-1-pole-dual-function-breaker-instruction-sheet-enfrsp.pdf
  4. Schneider Electric, TIME SAVER Diagnostics brochure 998-21300402_GMA-US — https://www.se.com/us/en/download/document/998-21300402_GMA-US/
  5. Schneider Electric FAQ000221049, AF/AFGF breaker with blinking LED — https://www.se.com/us/en/faqs/FAQ000221049/
  6. Schneider Electric instruction bulletin GDE27608 — https://www.se.com/us/en/download/document/GDE27608/
  7. Eaton IL003022EN, BR/CL/CH/QB AFCI, GFCI, GFEP and dual-function AF/GF instructions — https://www.eaton.com/content/dam/eaton/products/electrical-circuit-protection/molded-case-circuit-breakers/eaton-resi-installation-instructions-il003022en-en-us.pdf
  8. Eaton knowledge base, blinking red light on CH/BR dual-function breaker — https://eaton.my.site.com/publicknowledge/s/article/Blinking-red-light-on-CH-BR-dual-function-breaker
  9. Siemens AFCI-GFCI Circuit Breaker Diagnostic Guide — https://assets.new.siemens.com/siemens/assets/api/uuid:d10cec71-f518-4f35-83c4-cd40e8c308ab/afci-gfci-guide-compressed.pdf
  10. Siemens CAFCI troubleshooting white paper — https://cache.industry.siemens.com/dl/files/711/109774711/att_1008749/v1/SIE_WP_CAFCITroubleshooting.pdf
  11. ABB Electrification publication library, DFCI installation & instruction — https://electrification.us.abb.com/publibrary/product/dual-function-circuit-interrupter-dfci/installation-and-instruction
  12. ABB THQL1120AF2 combination AFCI installer instructions, distributor-hosted copy — https://uisupplies.com/Portals/1/Downloads/ABB%20THQL1120AF2%20Installation%20Instructions.pdf
  13. Leviton Load Center status indicator sheet — https://leviton.com/content/dam/leviton/residential/product_documents/load_center_misc/Load-Center-Status-Indicator-Sheet.pdf
Square D, QO, Homeline, Eaton, Siemens, GE, ABB, Q-Line, and Leviton are trademarks of their respective owners. Morningstar Electric LLC is not affiliated with or endorsed by them.
Reference only — not engineering, legal, or code-compliance advice. Results are estimates for qualified persons and must be verified against the NEC edition adopted where the work is done (your selected edition), manufacturer instructions, and the local AHJ. Use is subject to the Terms of Use & Disclaimer. — Morningstar Electric LLC