Megger / Insulation Resistance Basics
⌂ Home

Megger / Insulation Resistance Basics

General field practice for qualified electricians. The equipment manufacturer's instructions, your adopted code edition, and the AHJ govern where they differ.

⚠ An insulation tester puts out up to 1,000 V DC or more. Test only de-energized, locked-out, verified circuits. Warn others nearby. Conductors and cable can stay charged after the test, so let the tester discharge them, or discharge them yourself, before handling.

1 · What it measures

A megohmmeter applies a DC test voltage between a conductor and ground, or between conductors, and reads the leakage resistance in MΩ. Good insulation reads high and steady. Moisture, contamination, damage, and aging all lower the reading.

2 · Before you test — isolate electronics

3 · Test voltage and minimum readings

For acceptance testing of new equipment, ANSI/NETA ATS Table 100.1 lists minimum test voltages and minimum insulation resistance by equipment rating.[1] Common low-voltage rows:

Equipment ratingMinimum test voltageMinimum IR
250 V500 V DC25 MΩ
600 V1,000 V DC100 MΩ

Check the current NETA edition and the equipment manufacturer's values, which govern. Megger's field rule of thumb for in-service equipment is at least 1 MΩ per 1,000 V of operating voltage, with a 1 MΩ minimum.[2] Trends matter more than a single reading.

4 · Doing the test

  1. Lock out, verify absence of voltage, and isolate electronics (section 2).
  2. Check the tester: short the leads (about 0 Ω), then open them (above range).
  3. Test each conductor to ground (EGC or raceway), then conductor to conductor.
  4. Apply the test voltage for 1 minute and record the reading. Insulation charges up, so the reading should rise and then settle.
  5. Record the temperature and humidity. Insulation resistance drops as temperature rises, so correct to a common base (often 20 °C or 40 °C) when you trend readings.
  6. For motors and transformers, a polarization index (PI = 10-min reading ÷ 1-min reading) shows insulation condition. Megger's guide rates below 1 as dangerous, 1–2 questionable, 2–4 good, and above 4 excellent.[2]
  7. Let the tester discharge the circuit, reconnect, and restore.

Sources

  1. NETA tables (ATS/MTS Table 100.1, insulation resistance test values), government contract attachment copy — https://govtribe.com/file/government-file/75n99021r00025-sow-rmlcampus-electrical-maintenance-attachment-b-neta-tables-june-2021-dot-pdf
  2. Megger, "A Stitch in Time" — The Complete Guide to Electrical Insulation Testing — https://assets.tequipment.net/assets/3/7/A-Stitch-In-Time.pdf
Reference only — not engineering, legal, or code-compliance advice. Results are estimates for qualified persons and must be verified against the NEC edition adopted where the work is done (your selected edition), manufacturer instructions, and the local AHJ. Use is subject to the Terms of Use & Disclaimer. — Morningstar Electric LLC