Checking a Generator Interlock & Inlet
⌂ Home

Checking a Generator Interlock & Inlet Before First Start

General field practice for qualified electricians. The equipment manufacturer's instructions, your adopted code edition, and the AHJ govern where they differ.

⚠ Backfeed kills line workers. The utility main and the generator breaker must never be ON at the same time. Run portable generators outdoors only, far from windows, doors, and vents. CDC guidance is at least 20 ft from the home.[1]

1 · Paperwork & parts

2 · Mechanical interlock check (power off)

  1. With the main ON, try to turn the generator breaker ON. The interlock must block it.
  2. With the generator breaker ON, try to turn the main ON. It must be blocked.
  3. The backfed generator breaker is secured with a hold-down or retainer. 408.36(D) requires a backfed plug-in breaker to be secured by an additional fastener.
  4. The cover is installed with every screw and the interlock plate slides freely.

3 · Inlet & wiring

4 · Pre-start electrical checks

  1. Utility ON, generator breaker OFF: measure across the inlet pins (X–Y, X–W, Y–W, X–G, Y–G). Every reading must be 0 V. Any voltage means a wiring error or a failed interlock. Stop and fix it.
  2. With everything off, check continuity between inlet G and the panel ground bar, and between inlet W and the neutral bar. Check that the hots are not shorted to each other, the neutral, or ground.

5 · First start

  1. Turn the main OFF and lock it if possible. Turn every branch breaker OFF. Slide the interlock and turn the generator breaker ON.
  2. Start the generator with no load connected. Check its output at the generator outlet: ≈120/120/240 V and about 60 Hz.
  3. Shut the generator down, connect the cord to the inlet, and restart.
  4. At the panel, measure L1–N ≈ 120 V, L2–N ≈ 120 V, and L1–L2 ≈ 240 V.
  5. Turn on loads one at a time, largest first, staying within the generator's running watts. Watch the voltage.
  6. Return to utility: turn the generator breaker OFF, slide the interlock, turn the main ON, then shut down the generator.

Sources

  1. CDC, carbon monoxide poisoning basics (generators outdoors, at least 20 ft from windows, doors and vents) — https://www.cdc.gov/carbon-monoxide/about/index.html
Reference only — not engineering, legal, or code-compliance advice. Results are estimates for qualified persons and must be verified against the NEC edition adopted where the work is done (your selected edition), manufacturer instructions, and the local AHJ. Use is subject to the Terms of Use & Disclaimer. — Morningstar Electric LLC